€588.00 + VAT
In stock
In stock
3-phase filter with neutral IN: 440 Vac 50 A
Series | TYT |
---|---|
Code | XF50TYT8 |
Type | F50TYT8 (1) |
HS code | 85363030 |
GENERAL TECHNICAL DATA | |
Rated voltage | 440 Vac ± 10% |
Continuous current | 50 A |
Leakage current | 3 mA |
Frequency | 50…60 Hz |
Operating temperature range | -25…+85°C |
Isolation L / L | 1.45 kVdc / 60 s (2) |
Isolation L / PE | 2.25 kVdc / 60 s (2) |
Protection degree | IP 20 |
Connection terminal | fixed screw terminal blocks |
Housing material | metallic |
Dimensions (LxHxD) | 124x194x104 mm |
Approximate weight | |
Mounting information | screw fixing, on metal panel |
Common mode (L/PE) attenuation (dB) | |
0.15 MHz | 25 |
0.5 MHz | 45 |
1 MHz | 45 |
5 MHz | 40 |
10 MHz | 40 |
30 MHz | 25 |
Differential mode (L/PE) attenuation (dB) | |
0.15 MHz | 30 |
0.5 MHz | 50 |
1 MHz | 50 |
5 MHz | 40 |
10 MHz | 40 |
30 MHz | 30 |
ACCESSORIES | |
APPROVALS AND MARKINGS | ![]() |
For further information see PDF catalog
Copyright © Cabur srl Sede legale Località isola Grande, 45 – 17041 Altare (SV) – Italia – Tel. 019-589991 – Fax 019-58999233 – E-mail: info@cabur.it
Cap. Sociale: €2.000.000 Int. versato – Reg. Soc. Trib. Savona N° 4635 – C.C.I.A.A. N° 27269- Export N° SV 000532 – P.IVA e Cod. Fisc.: 00100760099
DISCLAIMER Cabur Srl may change and update any document available online without any obligation to inform users. Only cabur.it and cabur.eu domains are registered and maintained by Cabur srl. Cabur has no responsibility for contents published on sites under the same name, with different extensions from .it and .eu
for technical and commercial support
from monday to friday 8:30-12:30 13:00-17:00
+39 019 58999.219 customercare@cabur.it